Compatible model: ADC-AI- S300
Note: All values and settings must comply with applicable national and provincial/state standards, including local building codes and accessibility regulations.
Parameter table
Index | Parameter | Description | Function Behavior / Effect of Adjustment | Value | Default |
01 | Overload | Obstacle Detection Sensitivity | Lower values increase sensitivity, making the door stop or reverse more easily when resistance is detected during the opening cycle. Higher values decrease sensitivity, better handling wind or pressure but may delay obstacle detection. | 60-80 | 70 |
02 | Act Delay | Delay between trigger and activation of ADO (10th of Second) | Shorter delays cause the door to activate more quickly after receiving a trigger. Longer delays introduce a pause before activation. Increase delay if activation button is far from the door. | 0-99 | 0 |
03 | Backcheck Speed | Speed of the door at last 20 degrees | Controls the door speed during the final 20° of opening. The higher the value, the faster the speed. | 1-60 | 25 |
04 | Holding Time | Time (in seconds) that the door will stay open when reaching the backcheck zone | Longer times accommodate slower users or equipment. | 0-99 | 10 |
05 | Opening Speed | Door opening speed | Adjusts the speed at which the door opens. The higher the value the faster the speed. | 1-99 | 50 |
06 | Closing Speed | Door closing speed | Adjusts the speed at which the door closes. The higher the value the faster the speed. | 1-99 | 30 |
07 | Latch Speed | Door latching speed | Controls door speed during the final latching phase. The higher the value the faster the speed. | 1-99 | 10 |
08 | Control Mode | 1 = Regular, 2 = Unlocked washroom, 3 = Access control, 4 = Locked washroom | Selects the door’s operational logic. Each mode alters how the door responds to inputs and security features. | 1-4 | 1 |
09 | Sensor Cfg. | Safety sensor configuration selection | Specifies the number of connected safety sensors. A setting of 0 means no sensor is used. | 0-8 | 0 |
10 | Stop Speed | The speed of the door once presence detected via sensor on swing side | Works only if additional sensors are being used. | 1-60 | 10 |
11 | Power Close | Powered closing of door to positive latch (toggle) 0 = OFF, 1 = ON | Enables powered closing to fully latch the door. Useful in high-pressure environments or where positive latching is required. | 0-1 | 0 |
12 | Power Cls Spd | Power closing force adjustment | Adjusts the force applied during power closing. Higher values provide stronger force to overcome resistance. | 1-35 | 20 |
13 | Powr Cls Angle | Power Closing engage angle | Sets the door angle at which power closing begins. Larger angles start power closing earlier in the cycle. | 10-45 | 15 |
14 | Closing Time | Countown (in seconds) to full close | Sets the countdown duration for the door to fully close. | 0-50 | 50 |
15 | Opening Time | Countdown (in seconds) to full open | Sets the countdown duration for the door to fully open. | 0-50 | 50 |
16 | Latch Time | Countdown (in seconds) in latch cycle | Sets the countdown duration during the latch phase. When value is 0, allows for instant locking, use 2-8 for normal door functions, lower the value the earlier the locking. | 1-8 | 2 |
17 | Latch Angle | Latch cycle angle | Sets the angle at which the door will begin to slow before fully closing the door. Wider angles provide more control and adjustment in the final closing phase. | 1-45 | 20 |
18 | Decel Angle | Backcheck start angle | Sets the angle at which backcheck (deceleration) begins. | 20-110 | 80 |
19 | Preload Time | Pull time door before opening to release pressure (10th of second) | Sets the duration the door pulls in before opening to relieve pressure. Adjust the value if there’s trouble with an electric strike. | 0-50 | 0 |
20 | Preload Spd | Pull force of door before opening to release pressure | Adjusts the force of the preload pull before opening. | Fixed | 50 |
21 | Wind Brake | Turn ON/OFF wind break feature 0 = OFF, 1 = ON | When enabled, the wind brake helps resist wind pressure during door opening, improving stability in windy environments. Usage Note: | 0-1 | 0 |
22 | Wbrake Speed | Wind buffer force | Sets the strength of the wind buffer. | 1-99 | 10 |
23 | Wbrake Angle | Wind buffer engage angle | Defines the door angle where wind buffer engages. | 25-110 | 60 |
24 | Wbrake Sens | Wind buffer engage sensitivity | Adjusts the sensitivity for wind buffer activation. | 1-99 | 20 |
25 | Fire Al Mode | 0 = Smoke evacuation mode (door opens), | Sets behavior in fire alarm situations. | 0-1 | 0 |
26 | Easy Open | 0 = Heavy, 1 = Standard 15lbs, 2 = Light 5lbs | This refers to pounds of force needed to push the door manually. | 0-2 | 1 |
27 | Quick Open | 0 = Slow ramp from full closed, 1 = Standard ramp, 2 = Quick “kick-out” for fast opening | Sets acceleration profile from closed position. | 0-2 | 1 |
28 | Reactivate | 0 = No reactivation until fully closed, 1 = Allows reopening during closing, 2 = Touch-reverse on closing obstruction | Sets door behavior when a second open signal is received during the closing cycle. | 0-2 | 1 |
29 | Factory Test | 0 = Normal operating state, no reset action performed, 1 & 2 = Developer use only (for testing and debugging), 3 = Perform factory reset | Set the value to 3 to clear all user parameters and reboot the system. | 0-3 | 0 |