--- title: "Core Operating Parameters and Factory Reset" slug: "core-operating-parameters" updated: 2025-04-30T16:26:33Z published: 2025-04-30T16:26:33Z canonical: "ametawiki.ametagroup.com/core-operating-parameters" --- > ## Documentation Index > Fetch the complete documentation index at: https://ametawiki.ametagroup.com/llms.txt > Use this file to discover all available pages before exploring further. # Core Operating Parameters and Factory Reset ### Description: This section introduces typical settings for the ADC-AI-S300 door operator, including opening and closing cycle parameters. It also covers how to perform a factory reset to restore default settings. ### How to access the parameter setting menu 1. Ensure the door is fully closed — the control display should show **“DOOR CLOSED.”** 2. Press the **MENU** button on the control board to enter the **Main Menu**. 3. Use the **UP** and **DN** buttons to scroll until **[Settings]** appears on the screen. ![](https://cdn.document360.io/698fbf35-46b1-42c8-9a01-0506761ce4e8/Images/Documentation/image-1746029949400.png) 4. Press the **SEL** button to enter the **Settings** menu. 5. Scroll using **UP** and **DN** until the desired parameter and its current value are displayed. ![](https://cdn.document360.io/698fbf35-46b1-42c8-9a01-0506761ce4e8/Images/Documentation/image-1746030008205.png) 6. Press **SEL** again to edit the selected parameter. 7. Adjust the value using **UP** and **DN** until the desired setting is reached. 8. Press **SEL** to confirm and save the new value. 9. Press **BACK** to return to the **Basic Settings** menu and choose another parameter if needed. 10. Press **BACK** again to return to the **Main Menu**. ### Opening Cycle Settings ![Diagram of a opening cycle AI-generated content may be incorrect.](https://cdn.document360.io/698fbf35-46b1-42c8-9a01-0506761ce4e8/Images/Documentation/core-operating-parameters-image-c1a8o5lr.png) - **Index 05 – Opening Speed** Defines the speed at which the door opens. A higher value results in faster opening, while a lower value slows the motion. Adjust based on safety requirements and pedestrian flow. - **Index 03 - Backcheck Speed** Controls the door’s speed during the final 20° of the opening cycle (backcheck zone). A higher value increases speed; a lower value softens the door’s stop near full open. - **Index 18 – Deceleration Angle** Sets the angle at which the door begins to decelerate before entering the backcheck phase. Higher angles trigger earlier deceleration, resulting in a smoother and quieter stop. - **Index 04 - Holding Time** Sets how long (in seconds) the door remains open after reaching the backcheck position. Longer hold times are ideal for environments with slower pedestrians or equipment passage. - **Index 01 – Overload** Adjusts obstacle detection sensitivity during the opening cycle. Lower values increase sensitivity (door reacts faster to resistance), while higher values reduce sensitivity, allowing better performance against wind or pressure. ### Closing Cycle Settings ![A diagram of a closing cycle AI-generated content may be incorrect.](https://cdn.document360.io/698fbf35-46b1-42c8-9a01-0506761ce4e8/Images/Documentation/core-operating-parameters-image-znby1mjj.png) - **Index 06 – Closing Speed** Defines the speed at which the door closes. A higher value increases the closing speed, while a lower value ensures a slower, safer close - **Index 07 – Latch Speed** Controls the speed during the final latching phase. A higher value results in a faster latch; a lower value provides a gentler closing action to reduce noise and wear. - **Index 17 – Latch Angle** Sets the angle at which the door begins to decelerate before fully closing. A wider angle allows for smoother, more controlled final movement and better alignment with the door frame. ### Factory reset **Index 29 – Factory Test** - 0 = Normal operation (default) – no reset or action is triggered - 1 & 2 = Reserved for developer use only (used during internal testing and debugging) - 3 = Factory Reset – restores all parameters to default factory values and reboots the system Set the value to 3 to clear all user parameters and reboot the system. **When to Use:** - The door operator exhibits **unexpected behavior** or erratic motion due to misconfiguration. - You want to **erase all user-defined settings** and start fresh with factory defaults. - The unit is being **reinstalled or repurposed** in a new location or for a new application. - You're instructed by technical support to perform a system reset as part of troubleshooting. **Important:** After performing a factory reset, you must reinitialize the operator and reconfigure all relevant parameters before placing the unit back into service.